Notice: Trying to get property 'post_type' of non-object in /var/www/testnordic.com/en.testnordic.com/wp-includes/class-wp-query.php on line 4222
MIC-5005 Insulation Resistance Measurement | Testnordic.com
Deprecated: Unparenthesized `a ? b : c ? d : e` is deprecated. Use either `(a ? b : c) ? d : e` or `a ? b : (c ? d : e)` in /var/www/testnordic.com/en.testnordic.com/wp-content/plugins/responsive-menu-pro/vendor/twig/twig/lib/Twig/Node.php on line 42

MIC 5005

It is especially recommended for measurements in areas with very high electromagnetic disturbances

Description

MIC-5005 Insulation Resistance Measurement

MIC-5005 Insulation resistance measurement:

    • measurement voltage any in the range of 50…1000 V at 10 V and 1000…5000 V at 25 V resolution,
    • continuous indication of measured insulation resistance or leakage current,
    • automatic discharge of measured object capacitive voltage after the end of insulation resistance measurement,
    • acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
    • metered T1 , T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s,
    • adjustable measuring time to 99’59’’,
    • polarization index (PI) and dielectric absorption ratio (DAR) measurement,
    • indication of actual test voltage during measurement,
    • 1.2 mA and 3 mA test current,
    • step voltage insulation resistance measurement (SV),
    • Dielectric Discharge calculation (DD),
    • protection against measuring live objects,
    • measurements with test leads up to 20 m.
  • Digital filters function for measurements in high noise enviroment (10 s, 30 s , 60 s).
  • Measurement of leakage current during insulation resistance testing.
  • Measurement of capacitance during the measurement of RISO.
  • DC and AC voltage measurement in the range of 0…600 V.
  • 990 cells of memory (11880 records) with the capability of wireless data transmission to a PC or through a USB cable.
  • Power supply from battery packs, low battery warning indicator, built-in fast charger.
  • MIC-5005 Insulation Resistance Measurement has a display backlit.

The instruments meet the requirements of the EN 61557 standard.

Datasheet