RMO-TW series Winding Resistance Meter
RMO-TW Winding Resistance Meter is ideal for testing transformer windings (power transformers, distribution, autotransformers) and for on-load tap changer verification. In addition, any RMO-TW transformer ohmmeter & tap changer analyzer can also perform transformer demagnetization. The series contains 4 models, with maximal test currents from 10 A (RMO10TW) to 50 A (RMO50TW). They are fitted in a portable and lightweight metal housing.
All transformer ohmmeters from the RMO-TW series generate a true DC ripple-free current with automatically regulated measurement and discharging circuits. The injection of current and discharge of energy from the test object is automatically regulated. Three independent channels enable the testing of three windings in series. Consequently, this enables measurements of winding resistance in every tap position of an on-load tap changer without discharging between the tests.
DV-Win software enables control and observation of the test process, as well as saving and analyzing the results on a PC. This winding resistance meter provides a test report, arranged in a selectable form as an Excel spreadsheet, PDF, Word, or ASCII format. Additionally, DV-Win measures and calculates the OLTC transition time, the ripple and the winding resistance for each tap changing operation. The software can also perform the calculations necessary for the “Heat Run” test. Finally, a user can export all results in the form of a report.